Side Panel Installation
After ensuring the backplate has been properly and completely fastened to the wall, install the side
panels by inserting the side panel hooks into the rectangular cutouts in the backplate. The smooth
surface of the side panels are to face away from each other. All hooks must be engaged for proper
assembly; apply downward pressure as required to seat panels fully.
When the side panels are fully seated, the top surface will be flush with the internal 2U flanges in the
backplate and the bottom of the side panels will be flush with the bottom of the backplate. Two holes for
each side panel will align. Use four (4) of the supplied #12-24 screws for the two holes in each of
the left and right side panels. Ensure screws are installed before continuing installation.
Vent Tray Installation
Slide vent tray into the lower channel of the side
panels. The right angle flanges of the vent tray should
be oriented upward, toward the interior of the
cabinet. Temporarily install front panel (see
“Equipment Installation” on next page).